Operation Modes

Virtual PLC CPU operates under three distinct states. Each mode defines how the logic engine interacts with the project and the hardware.

Mode Definitions​

ModeStatusDescription
Stop🔴 InactiveThe PLC is idle and the logic program is loaded but not executed.
Run🟢 ActiveThe PLC is executing the logic program cyclically through the Scan Cycle.
Busy🟡 ProcessingActive during program transfers. Automatically switches to Stop once the process finishes.

The PLC Scan Cycle (Run Mode)​

When the CPU is in Run Mode, it executes a repetitive process known as a Scan. This cycle is critical for ensuring real-time response and consists of the following phases:

  1. Input Status Update: The CPU reads the physical/virtual status of all inputs.
  2. Logic Execution: The application program is processed sequentially using the previously read input data.
  3. Diagnostics & Comm: The system performs internal integrity checks and manages communication tasks.
  4. Output Update: The results of the logic execution are written to the outputs, and the cycle restarts.

:::info Cycle Time The total duration of the scan depends on the program size, the number of I/Os, and the volume of communication required. :::

Busy Mode Behavior​

This is a transient state. It is triggered exclusively when the EasyPLC Editor transfers a new logic program to the Virtual PLC CPU.

  • During this state, the CPU is locked for writing.
  • Once the transfer is successfully completed, the system defaults to Stop Mode for safety, awaiting a manual or commanded start.